ADPT-UP Differential Ultra-Low Air Pressure Transmitter w/LCD


Price:
Sale price£218.00

Description

The Ultra Low Pressure Transmitter is used to measure differential pressure up to 1”wc or 250 Pa and transmit via Analog and BACnet® Communications (latter optional).
 

It combines precision high sensitivity silicon sensing capabilities and the latest ASIC technology to substantially reduce offset errors due to changes in temperature, stability to warm-up, long term instability and position sensitivity. It is ideal for monitoring pressure for air or other clean inert gas. It features bi-directional pressure measurement, an on-board auto-zero function, a backlight LCD to display the pressure value and an optional alarm relay with variable trip points. The device is field-configurable via the local menu or the BACnet® connection. A weatherproof Polycarbonate enclosure with a hinged and gasketed cover is provided for ease of installation.


An optional on-board relay output, which is field adjustable, allows for an alarm function as well as an LCD (Alarm relay and LCD are standard on BACnet model).
Please contact us if you require 60Pa Model,  Relay option or BACnet MS/TP versions.

 

 

Features

  • Ranges between -0.125”WC and 1”WC (-30 Pa and 250 Pa)
  • Analog output or BACnet® communications
  • 8 selectable pressure ranges on analog model
  • 2 selectable pressure ranges on BACnet® model
  • 3 switch selectable current or voltage outputs
  • LCD display
  • Optional alarm relay output
  • Polycarbonate enclosure with hinged and gasketed cover

Specifications

  • ACCURACY ±1% F.S. of selected range @ 22°C (72°F) including hysteresis, non-linearity and repeatability
  • PRESSURE RANGE
    UPF1B: ±1 “WC or ±250 Pa  (BACNet)
    UPF2B: ±0.25 “WC or ±60 Pa  (BACNet)
    UPF1A: ±1”, 0-1”, ±0.5”, 0-0.5 “WC, ±250, 0-250, ±125, 0-125 Pa  (Analog)
    UPF2A: ±0.25”, 0-0.25”, ±0.125”, 0-0.125 “WC, ±60, 0-60, ±30, 0-30 Pa (Analog)
  • STABILITY <±1% F.S.O. (1 year)
  • THERMAL EFFECTS ±2% F.S. maximum, 10 to 40°C (50 to 104°F)
  • RESPONSE TIME
    BACnet®: 1 to 60 seconds, menu or BACnet® selectable
    Analog: 1 to 60 seconds, menu selectable
  • PROOF PRESSURE
    UPF1: 100 “WC (24.9 kPa)
    UPF2: 40 “WC (9.96 kPa)
  • BURST PRESSURE
    UPF1: 200 “WC (49.8 kPa)
    UPF2: 80 “WC (19.9 kPa)
  • OPERATING CONDITIONS 0 to 50°C (32 to 122°F), 5 to 95 %RH, non-condensing
  • MEDIA COMPATIBILITY Dry air or inert gas
  • ZERO ADJUSTMENTS Pushbutton, digital input auto zero, or via BACnet®
  • POWER SUPPLY 24 Vac/dc ±10%
  • POWER CONSUMPTION
    Analog: 37 mA maximum
    BACnet®: 52 mA maximum 
  • INPUT VOLTAGE EFFECT Negligible over operating range
  • PROTECTION CIRCUITRY Reverse voltage protected and output limited
  • OUTPUT SIGNAL 3-Wire: 4-20 mA, 0-5 or 0-10 Vdc, field selectable
  • OUTPUT DRIVE CAPABILITIES
    Current: 750 Ω maximum
    Voltage: 2,000 Ω min
  • DISPLAY
    Size: 38.1 x 16.5 mm (1.5” x 0.65”)
    Digit Height: 11.43 mm (0.45”)
    Symbols: “WC, Pa
    Backlight: Enable/disable/auto
  • ALARM FUNCTIONS (Optional)
    Relay Output: N.O. contact, 2 Amps @ 120 Vac or 30 Vdc
    Relay Trip Point: Upper and lower alarms adjustable over the pressure range
    Relay Delay: 0 to 10 minutes, via keypad or BACnet®
  • BACnet®  (Optional)
    Communications: 2-Wire RS-485, BACnet® MS/TP protocol
    Baud Rate: Locally set to 9600, 19200, 38400, or 76800
    MAC Address Range: Locally set to 0-127 (factory default is 3)
  • STORAGE TEMPERATURE -30 to 60°C (-22 to 140°F)
  • WIRING CONNECTIONS Screw terminal block
  • PRESSURE CONNECTIONS Barbed ports for 1/8” to 3/16 ID tubing
  • CONDUIT CONNECTION Access hole for 1/2” NPT conduit or cable gland
  • ENCLOSURE
    B: Grey Polycarbonate UL94-V0, IP65 (NEMA 4X)
    F: Same as B, with thread adapter (1/2” NPT to M16) and cable gland fitting
  • APPROVALS CE, RoHS
  • COUNTRY OF ORIGIN Canada

Technical

  ADPT-UP Differential Ultra Low Air Pressure Transducer Datasheet

Applications

  • HVAC (Heating, Ventillation and Air Conditioning) systems / VAV (Variable Air Volume) systems
  • Process Control
  • Air Flow Monitoring
  • Drop Across Air Filters
  • Static Building Pressure
  • Room Pressure Monitoring

Estimate shipping

You may also like

Recently viewed