The Air Flow and Velocity Transmitter series is intended for use in commercial environments. It is designed with a duct mount probe and adjustable collar suitable for round or rectangular ducts. The transmitter provides separate readings for air velocity and temperature. It comes with three measurement ranges in a single device (0–2 m/s, 0–10 m/s, 0–20 m/s) and is available with optional display and relay.
VELOCITY RANGES Base & Metric Models: 0-2, 10 & 20m/s, field selectable
VELOCITY ACCURACY Metric: Range - 0...2 m/s: <0.2 m/s + 5% from reading Range - 0...10 m/s: <0.5 m/s + 5% from reading Range - 0...20 m/s: <1.0 m/s + 5% from reading
THERMAL SHIFT ±0.8 %FS / °C
CALIBRATION Units calibrated at 22°C (71.6°F). Rapid thermal shift stabilization time 10 min.
TEMPERATURE RANGE 0 to 50°C (32 to 122°F)
TEMPERATURE ACCURACY <0.5°C for velocity >0.5 m/s (<0.9°F for v > 100 fpm)
OPERATING CONDITIONS 0 to 50°C (32 to 122°F), 0 to 95 %RH, non-condensing
STORAGE TEMPERATURE -20 to 70°C (-4 to 158°F)
MEDIA COMPATIBILITY Dry air or non-aggressive gases
OUTPUT SIGNAL 1 (TOUT) 0-10 Vdc (linear to temperature) L min 1K Ω 4-20 mA (linear to temperature) L max 400 Ω
OUTPUT SIGNAL 2 (VOUT) 0-10 Vdc (linear to m/s) L min 1K Ω 4-20 mA (linear to m/s) L max 400 Ω