Description
The CD2RMC Carbon Dioxide Transmitter series use a highly accurate and reliable Dual wavelength,Non-dispersive Infrared (NDIR) sensor in an attractive, low profile enclosure for room applications to monitor CO2, levels. A linear analog signal output of 4-20 mA, 0-5 or 0-10 Vdc is provided for connection to a building automation system. Optional features such as manual override and adjustable relay output are available.
Features
- Menu driven set-up
- 0-5000 PPM CO2 ranges
- Patented self-calibration algorithm
- Guaranteed 5 year calibration interval
- Easily field calibrated
Specifications
- GAS TYPE DETECTED Carbon Dioxide (CO2 )
- SENSOR TYPE Dual wavelength non-dispersive infrared (NDIR)
- SENSOR ACCURACY ± 50ppm + 3% of reading
- MEASUREMENT RANGE 0-2000ppm (default), adjustable 1000 - 5000ppm
- PRESSURE DEPENDENCY <1% of reading / kPa
- RESPONSE TIME 90 seconds (T90)
- WARM-UP TIME 1 minute
- SENSOR COVERAGE AREA 100 m2 (1000ft2 ) typical
- SENSOR LIFE SPAN >10 years
- TRANMSITTER ACCURACY ±0.25% of span (including linearity, hysteresis and repeatability)
- POWER SUPPLY 24 Vdc ±20% or 24 Vac ±10% (non-isolated half-wave rectified)
- PROTECTION CIRCUITRY Reverse voltage protected and transient protected
- INPUT VOLTAGE EFFECT Negligible over specified operating range
- OUTPUT SIGNAL TYPE 4-20 mA (3-wire), 0-5 or 0-10 Vdc (field selectable)
- CURRENT CONSUMPTION Current: 75 mA @ 24 Vdc max, 150 mA @ 24 Vac max Voltage: 50 mA @ 24 Vdc max, 100 mA @ 24 Vac max
- OUTPUT DRIVE @ 24 VDC Current: 550Ω max Voltage: 10,000Ω min
- AMBIENT OPERATING RANGE -10 to 50°C (14 to 122°F), 5 to 90 %RH non-condensing
- STORAGE TEMPERATURE -30 to 70°C (-22 to 158°F)
- STORAGE HUMIDITY 5 to 90 %RH non-condensing
- LCD DISPLAY Units: ppm (CO2 ), °C/°F (optional temperature/setpoint) Range: 0 to 5000ppm, 0 to 50°C (32 to 122°F) Resolution: 1ppm CO2 , (0.1°C/°F for optional temperature sensor) Size: 35mm W x 15mm H (1.4” x 0.6”), 2 lin x 8 character, alpha-numeric Digit Height: 2-line x 8 character
- OPTIONAL RELAY (2-WIRE OUTPUT) Selectable CO2 high, CO2 low, Temp High or Temp Low Rating: Form A (N.O.), 2 Amps @ 140 Vac / 30 Vdc
- OPTIONAL OVERRIDE SWITCH (2-WIRE OUTPUT) Front panel pushbutton Rating: 50 mA @ 12 Vdc max
- ENCLOSURE Material: ABS, White Dimensions: 84mm W x 119mm H x 29mm D (3.3” x 4.7” x 1.15”) Protection: IP30 (NEMA 1)
- WIRING Screw terminal block (14 to 22 AWG)
- APPROVALS CE, RoHS
- COUNTRY OF ORIGIN Canada