Description
The CEDT series uses a highly accurate and reliable non-dispersive infrared (NDIR) sensor in a duct mount enclosure to monitor return air CO2 levels for indoor applications. The compact dual wavelength CO2 sensor achieves excellent performance characteristics, including high accuracy and low power consumption to ensure stable long term operation. The CE features both 4-20 mA and voltage outputs (0-5 / 0-10 Vdc) for simple integration into any building automation system for the improvement of energy savings and to assure good indoor air quality. The device is also available with an optional resistive temperature sensor.
F model with Cable Gland fitting
Features
- Dual wavelength NDIR
- Selectable outputs
Specifications
- CO2 SENSOR Dual wavelength non-dispersive infrared (NDIR)
- RANGE 0-2000 ppm
- ACCURACY ±(50ppm +3% of reading)
- PRESSURE DEPENDENCY <1% of reading / kPa
- RESPONSE TIME 2 minutes (T90)
- WARM-UP TIME 1 minute
- SENSOR LIFE SPAN >10 years
- POWER SUPPLY 24 Vac/dc ±20% (non-isolated half-wave rectified) CONSUMPTION 80 mA max @ 24 Vdc, 160 mA max @ 24 Vac
- PROTECTION CIRCUITRY Reverse voltage and transient protected
- OUTPUT SIGNALS 4-20 mA, 0-5 Vdc, 0-10 Vdc (field selectable)
- DRIVE CAPABILITY @ 24 VDC Current: 600Ω maximum Voltage: 10 KΩ minimum
- OPERATING CONDITIONS 0 to 50°C (32 to 122°F), 0-95 %RH non-condensing
- OPTIONAL TEMPERATURE SENSOR Various thermistors or RTD’s as a 2 wire resistance output
- WIRING CONNECTIONS Screw terminal block (14 to 22 AWG)
-
ENCLOSURE B: Polycarbonate, UL94-V0, IP65 (NEMA 4X)
F: Same as B with thread adapter (1/2” NPT to M16) and cable gland fitting - PROBE 152mm L x 21.6mm D (6” x 0.85”)
- APPROVALS CE, RoHS
- COUNTRY OF ORIGIN Canada