Description
The CR3 Series Cleanroom Monitor, was developed specifically to allow for monitoring of confined spaces with accuracy and reliability. The CR3 allows for either in-room or remote monitoring with three different models; integrated sensors, remote sensors or display only to suit a variety of installation needs. It features a flush fitting stainless-steel front plate that enables the user to wipe-down the unit when necessary.
The CR3 allows for more efficient measurement of three critical parameters; humidity, temperature and pressure, in one flush mount enclosure. It is equipped with sensors with best in class accuracies to match cleanroom requirements, and can communicate with the building automation system via Modbus, BACnet® or Analog outputs. It is powered by a standard 24 Vdc or 24 Vac power supply.
Features
- Humidity, Temperature & Pressure
- BACnet®, Modbus or Analog Outputs
- In-room or Remote Monitoring
- Individual alarms for ALL parameters
- Large Easy-To-Read Display
Specifications
-
TEMPERATURE INPUT
Sensor Type: 10KΩ NTC
Thermistor Temperature Range: 0 to 50°C (32to 122°F)
Accuracy: ±0.2°C (±0.4°F) curve matched -
RELATIVE HUMIDITY INPUT
Sensor Type: Thermoset polymer based capacitive
RH Range: 0 to 100 %RH Accuracy: ±2 %RH
Hysteresis: ±1.5 %RH
Stability: ±1.2 %RH typical @ 50 %RH in 5 years -
DIFFERENTIAL PRESSURE INPUT
Sensor Type: MEMS piezo resistive differential
Pressure Ranges:
01 - ±250Pa or ±25mmWC,
02 - ±500Pa or ±50mmWC
Accuracy: ±0.5 %FS
Stability: ±0.5 %FS max 1 year
Thermal Effect: <±1 %FS, 0 to 70°C (32 to 158°F)
Proof Pressure: 24.9 kPa (2490 mmWC)
Burst Pressure: 74.7 kPa (7470 mmWC)
Media Compatibility: Dry air or inert gas -
INDICATION
Temperature Display: 3 digit LED as 0.0-50.0°C or 32.0-122°F (°C/°F by LED)
Relative Humidity Display: 3 digit LED as 0.0-99.9 %RH
Differential Pressure Display: 3 1/2 digit LED display as -500-500 Pa or -50.0-50.0 mmWC (Pa / mmWC is indicated by an LED)
Digit Type: 7 segment red LED, 0.80” (20.32 mm) high
Alarm Indication: Low / High alarm red LED for each parameter (T + RH + DP) -
USER INPUT
Programming: Menu / Up / Down front panel tactile keys
Alarm Silence: Silence front panel tactile key -
ANALOG OUTPUTS
Signal Type: 4-20 mA (sourcing) and 0-5 Vdc / 0-10 Vdc selectable
Number of Outputs: 3 (Temp, RH, DP)
Output Drive:
Current - 500Ω max,
Voltage - 10 KΩ min
Output Scales: 0 to 50°C, 0 to 100 %RH, ±500 Pa -
ALARM OUTPUTS
Number of Outputs: 3 (Temp, RH, DP), can assign condition as low/high/both
Output Type: NO optically isolated solid state FET switch
Contact Rating: 100 mA at 28 Vac / 40 Vdc maximum
Trip Point: Upper and Lower alarms adjustable
Alarm Delay: 0 to 255 seconds (programmable)
Operation: Self-resetting, non-latching
Alarm Buzzer: Internal, operates on any alarm condition
Buzzer Delay: 0-255 seconds (programmable)
Operations: Self-resetting, can be silenced via silence button or disabled remotely via BACnet® or Modbus -
COMMUNICATION
Hardware: Isolated 2-wire RS-485 MS/TP
Software: Modbus RTU or BACnet®
Baud Rate: 9600, 19200, 38400, 57600, 76800 or 115200
Address Range: Modbus - 1-255, BACnet® - 0-127 - OPERATING CONDITIONS 0 to 50°C (32 to 122°F), 0-90 %RH non-condensing
- STORAGE TEMPERATURE -20 to 60°C (-4 to 140°F)
- POWER SUPPLY 24-30 Vdc / 20-26 Vac
- POWER CONSUMPTION 200 mA max
- WIRING CONNECTIONS Pluggable screw terminal block (14 to 22 AWG)
- PRESSURE CONNECTIONS Port for 1/8” ID tubing
- PROTECTION IP65 front plate
- ENCLOSURE Wall mount enclosure, SS304, suitable for wipe-down 255mm W x 182.5mm H x 36mm D (8.86” x 7.19” x 1.46”)
- WEIGHT 1.3 kg
- CERTIFICATION CE, RoHS
- COUNTRY OF ORIGIN Canada
Technical