GDTCNCSM Nitrogen Dioxide and CO Sensor, Analog Output (IP65)


Price:
Sale price£466.00

Description

The GDT Series of gas monitoring sensors monitor levels of carbon monoxide (CO) and/or nitrogen dioxide (NO2) to provide an early warning of elevated concentrations.

The GDT is available as a standalone CO or NO2, as well as a CO/NO2 dual sensor device. The dual sensor device is available in 2 configurations: CO/NO2 housed one enclosure or as CO with remote NO2 sensor for mounting at a higher location.

The GDT gas sensors are encapsulated in field replaceable sensors pods that are located on the bottom of the enclosure. The pod design provides a greater area of gas sampling then that of devices that utilize a single vent hole. Replacement pods come pre-calibrated and ready for installation.

The GDT is available with either Analog, BACnet or Modbus outputs for communication with a building automation system. Standard features include LCD display for configuration and local display as well as status LED’s. Optional features include: 1 or 2 adjustable control/alarm relays, adjustable audible (buzzer) & visual (strobe) alarms as well as various temperature sensor.

The GDT is housed in an IP65 polycarbonate enclosure with a hinged and gasketed cover that provides ease of installation and access for set up and configuration.

 

Please specify in the Order comments field, whether you need Analog Output or DC Voltage Output options, Concealed or Visible LCD display.

For Relay, Audible/Visual Alarm, Temperature Sensor or BACnet MSTP/Modbus RTU options, please contact us.

Features

  • Setup/calibration fully menu driven
  • Selectable ranges of 0-100, 150, 300, 400 or 500 ppm
  • Replaceable Electrochemical sensing element
  • Optional on board relays with field adjustable trip point.
  • Optional BACnet or Modbus communications
  • Powered by either an AC or DC source
  • Choice of three field adjustable analog output signals
  • Easy to calibrate in the field

Specifications

Specifications for all Models

GAS TYPE DETECTED Carbon Monoxide (CO) and/or Nitrogen Dioxide (NO2 )
SENSOR TYPE  Electrochemical, diffusion sampling
SENSOR APPROVALS  CO Sensor is a UL approved component for UL 2075/with UL 2034, File No. E240671
SENSOR ACCURACY 

Carbon Monoxide: ±5 ppm or ±5% of reading
Nitrogen Dioxide: ±0.2 ppm or ±5% of reading

MEASUREMENT RANGE  Carbon Monoxide: 0-500 ppm, adjustable 100-500 ppm
Nitrogen Dioxide: 0-10 ppm
RESPONSE TIME  < 30 seconds typical
WARM-UP TIME  1 minute
SENSOR COVERAGE AREA  700m2 (7500ft2 ) or 15m (50ft) radius
SENSOR LIFE SPAN  Carbon Monoxide: 5-7 years in air
Nitrogen Dioxide: 2 years
SENSOR REPRODUCIBILITY
(SAME DAY)
 ±2%
LONG TERM DRIFT  Carbon Monoxide: <5% per year
Nitrogen Dioxide: Zero - <±2 ppm/year
                            Span - <2% signal/month
POWER SUPPLY  24 Vdc ±20% or 24 Vac ±10% (non-isolated half-wave rectified)
PROTECTION CIRCUITRY  Reverse voltage and transient protected
OUTPUT SIGNAL TYPE  4-20 mA (3-wire), 0-5 Vdc/0-10 Vdc, BACnet® or Modbus
NETWORK INTERFACE  Hardware: 2 wire RS-485
Software: Native BACnet® MS/TP or Modbus RTU
Baud Rate: Locally set 9600, 19200, 38400, 57600, 76800, or 115200
MAC Address Range: 0-255 (Factory default is 1) (128 devices max on one daisy chain)
CURRENT CONSUMPTION  425 mA @ 24 Vac max, 220 mA @ 24 Vdc max (test mode)
OUTPUT DRIVE @ 24 VDC Current: 550Ω maximum
Voltage: 10,000Ω minimum
AMBIENT OPERATING RANGE  -20 to 50°C (-4 to 122°F), 15 to 90 %RH non-condensing
STORAGE TEMPERATURE -30 to 60°C (-22 to 140°F)
LCD Viewable or concealed (with cover closed)
Units: ppm for CO/NO2 , °C/°F for optional temperature
Size: 35mm W x 15mm H (1.4” x 0.6”), alpha-numeric 2-line x 8 characters
Backlight: Enable or disable via menu
USER INTERFACE  Silence/Test button, Bi-color status LED, Red LED alarm indicator,
White high intensity LED strobe (optional)
OPTIONAL TEMPERATURE SIGNAL Type: Thermistor or RTD
Accuracy:
Thermistors - ±0.2˚C (±0.36˚F) @ 25˚C (77˚F)
Platinum RTD’s - ±0.3˚C (±0.54˚F) @ 0˚C (32˚F)
Nickel RTD’s - ±0.4˚C (±0.72˚F) @ 0˚C (32˚F)
Output: 2-wire resistive

Type: Analog, BACnet® or Modbus
Sensor Accuracy: ±0.2°C (±0.36˚F)
Range: -20 to 50°C (-4 to 122°F) or 0 to 50°C (32 to 122°F) (field selectable)
Output: Analog - 0-5/0-10 Vdc or 4-20mA (As per output selected)
              BACnet®/Modbus - Network Variable
OPTIONAL RELAY OUTPUTS  Contact Ratings: Form C (NO + NC), 5 Amps @ 140 Vac, 5A @ 30 Vdc Relay Setpoint + Hysteresis: Programmable via menu Relay Time Delay: Programmable via menu
OPTIONAL ALARM  Audible: Buzzer, 93dB @ 30 cm Visual: High intensity white LED strobe
MAIN ENCLOSURE  Material/Rating: Grey Polycarbonate, UL94 V0, IP65 (NEMA 4X) with Security Screw installed
Dimensions Incl. Sensor Pod: 202.3mm H x 184mm W x 54.3mm D (8” x 7.24” x 2.15”)
Weight Incl. Sensor Pod: 515 grams (1.14 lbs)
REMOTE NO2 ENCLOSURE  Material/Rating: Grey Polycarbonate, UL94 V0, IP65 (NEMA 4X)
Dimensions Incl. Sensor Pod: 109.5mm H x 83.3mm W x 52mm D (4.31” x 3.28” x 2.05”)
Weight Incl. Sensor Pod: 109 grams (0.24 lbs)
WIRING CONNECTIONS  Screw terminal block (14 to 22 AWG), Top or bottom conduit entry 22.73mm (0.875”) hole
APPROVALS  CE
COUNTRY OF ORIGIN  Canada

 

Technical

GDT Series Combined CO and NO2 sensor datasheet