Description
The GW-5492 is a fully configurable universal Modbus RTU to BACnet/IP gateway. The GW-5492 includes a BACnet/IP Server and Modbus RTU Master, which is used to make Modbus RTU devices (such as the M-7000 range or various Meters or PLC's etc) accessible on a BACnet network.
BACnet (Building Automation and Control Networking) protocol has been designed specifically to meet the communication needs of building automation and control systems for applications such as heating, ventilating, air-conditioning control…etc.
The GW-5492 contains a large number of BACnet objects (AI, AO, AV, BI, BO, BV, MSI, MSO, MSV) giving you flexibility in mapping Modbus RTU registers to any combination of BACnet objects. Multiple BIBBs (DS-RP-B, DS-RPM-B, DS-WP-B, DS-WPM, DS-COV-B…etc.) are supported. All the data transfer is configurable using a standard Web browser.
Features
General Features
-
Quick and Cost Effective network integration
-
Provides PWR/Communication Status indication LED's
-
Read/Write to any standard Modbus register via BACnet
-
No Programming Required
-
Modbus register mapping configured via web interface
BACnet
-
Fully Compliant with BACnet/IP Server
-
Supports up to 200 objects each of types: Analog Input, Analog Output, Analog Value, Binary Input, Binary Output, Binary Value, Multi-State Input, Multi-State Output
-
BIBB (BACnet Interoperability Building Blocks) Supported: DS-RP-B, DS-RPM-B, DS-WP-B, DS-WPM-B, DS-COV-B, DM-DDB-B, DM-DOB-B, DM-DCC-B, DM-TS-B, DM-UTC-B, DM-RD-B
Modbus RTU
-
Fully User Configurable Modbus RTU Slave
-
Supports Modbus coils, input register, holding registers
-
Supports for Function Code 0x01, 0x02, 0x03, 0x04, 0x05, 0x06, 0x10, 0x0F
-
Baud rates supported: 2400, 4800, 9600, 19200, 38400, 57600, and 115200 bps
-
Configured via standard web browser
-
Provide Modbus network configuration interface
-
Provide BACnet configuration interface
Specifications
System
|
|
CPU
|
32-bit
|
SDRAM
|
128 MB
|
Flash
|
64 MB
|
EEPROM
|
16 KB
|
Communication Ports
|
|
COM1
|
RS-232 (RxD, TxD, and GND); Non-isolation
|
COM2
|
RS-485 (D2+, D2-); 2500 VDC; isolated
|
Ethernet
|
10/100Base-TX Ethernet Controller
|
Protocol
|
|
Modbus
|
Modbus RTU Master
|
BACnet
|
BACnet/IP Server
|
BACnet Objects
|
AI, AO, AV, BI, BO, BV, MSI, MSO, MSV (Maximum: 200 each)
|
BIBB Supported
|
DS-RP-B, DS-RPM-B, DS-WP-B, DS-WPM-B, DS-COV-B, DM-DDB-B, DM-DOB-B, DM-DCC-B, DM-TS-B, DM-UTC-B, DM-RD-B
|
Mechanical
|
|
Dimensions (W x L x H)
|
91mm x 132mm x 52mm
|
Installation
|
DIN-Rail
|
Environmental
|
|
Operating Temp.
|
-25 ~ +75 °C
|
Storage Temp.
|
-30 ~ +85 °C
|
Humidity
|
5 ~ 90% RH, non-condensing
|
Power
|
|
Input Range
|
+10 ~ +30 VDC
|
Isolation
|
1 kV
|
Consumption
|
4.8 W (0.2 A @ 24 VDC)
|
Technical
GW-5492 BACNet to Modbus RTU Datasheet
Applications
- Building Automation
- Heating, Ventilating, and Air-conditioning Control
- Lighting Control
- Access Control
- Fire Detection Systems