Couldn't load pickup availability
Free standard shipping on orders over £500
This device provides 8 channels capable of receiving 4-20mA inputs from a wide number of sensors with this type of output.
This unit comes complete with internal resistors, so no external resistors are needed.
| CPU Module | |
|---|---|
| Watchdog Timer | Module, Communication (Programmable) |
| Isolation | |
|---|---|
| Intra-module Isolation | 3000 VDC |
| EMS Protection | |
|---|---|
| EFT (IEC 61000-4-4) | ±4 kV for Power Line |
| ESD (IEC 61000-4-2) | ±4 kV Contact for Each Terminal |
| Surge (IEC 61000-4-5) | ±0.5 kV for Power Line |
| LED Indicators | |
|---|---|
| Status | 1 x Power and Communication |
| Analog Input | |
|---|---|
| Channels | 8 Differential |
| Type | Current |
| Range | ±20 mA, 0 ~ 20 mA, 4 ~ 20 mA |
| Resolution | 16-bit |
| Accuracy | Normal Mode: ±0.1% of FSR Fast Mode: ±0.5% of FSR (Only for I-7017FC) |
| Sampling Rate | Normal Mode: 10 Hz Fast Mode: 60 Hz (Only for I-7017FC) |
| Input Impedance | Current: 125 Ω |
| Common Voltage Protection | ±15 VDC |
| Overcurrent Protection | 50 mA at 110 VDC |
| Open Wire Detection | For 4 ~ 20 mA Only |
| COM Ports | |
|---|---|
| Ports | 1 x RS-485 |
| Baud Rate | 1200 ~ 115200 bps |
| Data Format | (N, 8, 1), (N, 8, 2), (E, 8, 1), or (E, 8, 2) |
| Protocol | DCON |
| Power | |
|---|---|
| Reverse Polarity Protection | Yes |
| Input Range | +10 ~ +30 VDC |
| Consumption | 1.3 W |
| Mechanical | |
|---|---|
| Dimensions (mm) | 72 x 123 x 35 (W x L x H) |
| Installation | DIN-Rail Mounting |
| Environment | |
|---|---|
| Operating Temperature | -25 ~ +75 °C |
| Storage Temperature | -40 ~ +85 °C |
| Humidity | 10 ~ 95% RH, Non-condensing |