I-7017R Voltage Input Module (8 channel),isol


Price:
Sale price£212.00

Description

The I-7017R is an 8-channel analog input module with an extra isolation, such as overvoltage protection of 240 Vrms.

The input type includes both voltage and current. The I-7017R is an upgraded version of the I-7017, with the only difference being that the I-7017R is much more suitable for critically harsh environments. The sampling rate of the I-7017R is adjustable, meaning that either fast mode or normal mode can be selected. The I-7017R also has 4 kV ESD protection as well as 3000 V
DC intra-module isolation.

The M-7017R ahas the same specification as the I-7017R, but provides additional support for the Modbus RTU protocol as well as the DCON protocol.

Features

  • I-7017R and M-7017R
    • 240 Vrms Overvoltage Protection
    • Voltage and Current Input
  • Adjustable Sampling Rate
  • 4 kV ESD Protection
  • 3000 VDC Intra-module Isolation
  • Dual Watchdog
  • RoHS Compliance
  • Wide Operating Temperature Range: -25 ~ +75°C

Specifications

Model I-7017R I-7017R-A5
M-7017R M-7017R-A5
Analog Input
Channels 8
Wiring Differential
Input Range ±150 mV, ±500 mV, ±1 V, ±5 V, ±10 V,
±20 mA, 0 ~ 20 mA, 4 ~ 20 mA
(requires an optional external 125 Ω resistor)
±50 V, ±150 V
Resolution 16-bit 16-bit
Accuracy Normal Mode 0.1%
Fast Mode 0.5 %
Sampling Rate Normal Mode 10 Hz
Fast Mode 60 Hz 50 Hz
Input Impedance Voltage 20 MΩ 290 kΩ
Current -
Common Voltage Protection ±200 VDC
Individual Channel Configuration - 
Overvoltage Protection 240 Vrms ±200 VDC
Overcurrent Protection -
Virtual Channel to Channel Isolation Yes, 400 VDC
Open Wire Detection for 4 ~ 20 mA Yes

 

Model I-7017R I-7017R-A5
M-7017R M-7017R-A5
Communication
Interface RS-485
Format (N, 8, 1)
Baud Rate 1200 ~ 115200 bps
Accuracy DCON
Modbus RTU, DCON
Dual Watchdog Yes, Module (1.6 Seconds), Communication (Programmable)
LED Indicator/Display
System LED Indicator Yes, 1 LED as Power/Communication Indicator
I/O LED Indicator -
7-Segment LED Display -
Isolation
Intra-Module Isolation,
Field-to-Logic
3000 VDC
EMS Protection
ESD (IEC 61000-4-2) ±4 kV Contact for each Terminal
EFT (IEC 61000-4-4) ±4 kV to Power Line
Surge (IEC 61000-4-5) ±0.5 kV for Power Line
Power
Reverse Polarity Protection Yes
Input Range 10 ~ 30 VDC
Consumption 1.3 W 1.6 W
Mechanical
Dimensions (W x L x H) 72 mm x 123 mm x 35 mm
Installation

Estimate shipping