The I-7065B provides 4 digital input channels and 5 DC SSR output channels. All digital input channels can be used as 16-bit counters. Additionally, the digital input channels can be selected either as sink- or source-type via wire connections.
In comparison to electromechanical relays, SSR technology provides a faster response time and greater electrical endurance. The integration of DC SSR technology also eliminates potential for arcing, bounce, and switching noise. The I-7065BD/M-7065BD provides 9 LED indicators that can be used to monitor the status of the digital input and SSR output. There are also options for configuring power-on and safe values. 4 kV ESD protection and 3750 VDC intra-module isolation are also provided to enhance noise protection capabilities in industrial environments. The M-7065B supports both the Modbus RTU and DCON protocols, which can be configured via software.
I/O Specifications
| |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Unit Specifications
| Models | I-7063B | I-7063BD | I-7065B | I-7065BD | M-7065B | M-7065BD |
| Communication | ||||||
| Interface | RS-485 | |||||
| Format | (N, 8, 1) (N, 8, 2) (E, 8, 1) (O, 8, 1) | |||||
| Baud Rate | 1200 ~ 115200 bps | |||||
| Protocol | DCON | Modbus RTU, DCON | ||||
| Dual Watchdog | Yes, Module (1.6 Seconds), Communication (Programmable) | |||||
| LED Indicator/Display | ||||||
| System LED Indicator | Yes, 1 LED as Power/Communication Indicator | |||||
| I/O LED Indicators | - | Yes, 11 LEDs as Digital Input/ Relay Output Indicators | - | Yes, 9 LEDs as Digital Input/ Relay Output Indicators | - | Yes, 9 LEDs as Digital Input/Relay Output Indicators |
| 7-Segment LED Display | - | |||||
| Isolation | ||||||
| Intra-Module Isolation, Field-to-Logic | 3750 VDC | |||||
| EMS Protection | ||||||
| ESD (IEC 61000-4-2) | ±4 kV Contact for each Terminal | |||||
| ±8 kV Air for Random Point | ||||||
| EFT (IEC 61000-4-4) | ±2 kV for Power Line | |||||
| Surge (IEC 61000-4-5) | - | |||||
| Power | ||||||
| Reverse Polarity Protection | Yes | |||||
| Input Range | 10 ~ 30 VDC | |||||
| Consumption | 0.5 W | 1.0 W | 0.6 W | 1.0 W | 0.6 W | 1.0 W |
| Mechanical | ||||||
| Dimensions (W x L x H) | 72 mm x 123 mm x 35 mm | |||||
| Installation | DIN-Rail or Wall Mounting | |||||
| Environment | ||||||
| Operating Temperature | -25 ~ +75°C | |||||
| Storage Temperature | -40 ~ +85°C | |||||
| Humidity | 10 ~ 95% RH, Non-condensing | |||||