Description
The I-87019ZW is a 10-channel universal analog input module with an RS-485 interface that is a specially designed for extremely accurate thermocouple measurement and features automatic cold-junction compensation for each channel to ensure temperature output consistency and stable temperature output in the field.
Besides the thermocouple inputs, the I-87019ZW also supports voltage and current inputs. The voltage input range can be form +/-15 mV to +/-10 V, and the current input range can be either 4 ~ 20 mA, 0 ~ 20 mA, or +/- 20 mA. Up to 10 analog inputs of different types can be connected to a single module. Overvoltage protection of up to 240 Vrms is provided. The module also features per-channel open wire detection for thermocouple and 4 ~ 20 mA inputs.
Features
- 10-channel Analog Input
- Individual Channel Configuration
- Open Thermocouple Detection
- Temperature Output Consistency
- Stable Temperature Output in the Field
- 240 Vrms Overvoltage Protection
- Jumper Selectable Voltage or Current Input
- 4 kV ESD Protection
- Dual Watchdog
- 3000 VDC Intra-module Isolation, Field-to-Logic
- Wide Operating Temperature Range: -25 °C ~ +75 °C
Specifications
I/O Specifications
Analog Input | ||
Input Channels | 10 Differential | |
Input Type |
+/-15 mV, +/-50 mV, +/-100 mV, +/-150 mV +/-500 mV, +/-1 V, +/-2.5 V, +/-5 V,+/-10 V -20 mA ~ +20 mA, 0 ~ 20 mA, 4 ~ 20 mA (Jumper Selectable) Thermocouple Type: (J, K, T, E. R. S, B, N, C, L, M, and LDIN43710) |
|
Resolution | 16-bit | |
Sampling Rate | 10 Samples/Second (Total) | |
Accuracy | +/- 0.1% | |
Zero Drift | +/- 20 μV/°C | |
Span Drift | +/- 25 ppm/°C | |
Common Mode Rejection | 86 dB | |
Normal Mode Rejection | 100 dB | |
Input Impedance | Voltage Input: >400 k[, Current Input: 125 Ω | |
Individual Channel Configuration | Yes | |
Overvoltage Protection | 240 Vrms | |
Open Thermocouple Detection | Yes, (Software Selectable) | |
ESD Protection | +/- 4 kV, Contact for Each Terminal | |
Intra-module Isolation, Field-to-Logic | 3000 VDC |
System Specifications
Interface | ||
Interface | RS-485 | |
Format | N, 8, 1; N, 8, 2; E, 8, 1; O, 8, 1 | |
Baud Rate | 1200 ~ 115200 bps | |
Watchdog | ||
Dual Watchdog | Yes, Module (1.6 seconds) and Communication (Programable) | |
LED Display | ||
1 LED as Power/Communication Indicator | ||
Power | ||
Power Consumption | Maximum : 1.4 W | |
Environment | ||
Operating Temperature | -25 °C ~ +75 °C | |
Storage Temperature | -40 °C ~ +85 °C | |
Humidity | 10 ~ 90% RH, Non-condensing | |
Dimensions | ||
I-87019ZW | 30 mm x 86 mm x 114 mm (W x L x H) | |
DB-1820 | 22 mm x 78 mm x 65 mm (W x L X H) | |
DN-1822 | 27 mm x 96 mm x 103 mm (W x L x H) |
Technical
Applications
Building Automation, Factory Automation, Machine Automation, Remote Maintenance, Remote Diagnosis, Testing Equipment.