LC-101 Lighting Control Module, 1 AC DigIn/1 RelayO


Price:
Sale price£39.00

Description

The LC-101 is an easy-to-use lighting control module that requires no specialist skills to install and operate, and no software is needed in order to control the DO channels.

The LC-101 provides 1 channel for AC Digital Input (photo couple isolation) and 1 channel for Relay Output. The output channel is form C type (NO/NC) power relay, while the input channel is based on a sink-type using a wire connection. The input channel can directly control the relay ON and OFF sequence without requiring a remote host controller. 4 kV ESD protection and 5000 Vrms intra-module isolation are also provided.

When required, communication with the LC-101 is programmable based on the Modbus RTU protocol, so multiple units can be connected when set to a different Node ID.

Ideal for use as part of a Building Management Systems or even with our range of TouchPAD displays/controllers.

Features

  • Cost-effective for lighting control
  • Power Relay Output
  • Isolated AC Digital Input
  • Tiny form-factor
  • Low power consumption

Specifications

Digital Input
Input Channels 1
Type 90 ~ 240 VAC
On Voltage Level 85 VAC
Off Voltage Level 60 VAC
Input Impedance 68 KΩ, 1 W
Isolation 5000 Vrms
Function Local and Remote Direct Control Relay ON/OFF and Remote Status Monitoring
Relay Output
Output Channels 1
Type Power Relay, Form C
Operating Voltage 250 VAC or 30 VDC
Max. Load Current NO: 10 A, NC: 6 A
Operating Time 15 ms Max.
Release Time 5 ms Max.
Electrical Life (Resistive load) 100,000 ops
Mechanical Life 20,000,000 ops at no load (300 ops/minute)
Power-on Value No
Safe Value No


System Specifications
 
Communication
Interface RS-485
Format N, 8, 1
Baud Rate 1200 ~ 115200 bps
Protocol Modbus RTU/DCON
Node Addresses Hardware Configuration: 32 ~ 63 Software Configuration: 0~255 for DCON and 1~247 for Modbus RTU standard)
Connector RJ-11(6P4C or 6P6C)
LED Display
Power 1 LED as Power Indicator
EMS Protection
ESD (IEC 61000-4-2) ±2 kV Contact for Each Terminal
±4 kV Air for Random Point
EFT (IEC 61000-4-4) ±2 kV for Power
Power Requirements
Input Voltage Range 10 ~ 30 VDC
Consumption 0.5 W Max.
Connector RJ-11
Mechanical
Dimensions (W x L x H)

Estimate shipping