Description
The M-7019R is an analog input module that includes 8 differential analog input channels. Voltage, current, or thermocouple input can be selected for all analog Input channels via a jumper, and each channel can be configured for an individual range. The voltage input range can be from ±15 mV to 10 V, the current input range can be either +4 to +20 mA, 0 to +20 mA, or ±20 mA, and types J, K, T, E, R, S, B, N, C, L, M, LDIN43710 can be used for the thermocouple input.
Up to 8 different analog input types can be connected to a single module. The module provides up to 240 Vrms overvoltage protection, 4 kV ESD protection, and 3000 VDC intra-module isolation also features per-channel open wire detection for the thermocouple and +4 ~ +20 mA input types. The M-7019R supports Modbus RTU and DCON protocols, which can be configured via software, and all hardware specifications are the same as the I-7019R.
Features
-
8 Universal Analog Inputs
-
Individual Channel Configuration
-
Jumper Selectable Voltage, Current or Thermocouple Input
-
High Over-voltage Input Protection
-
High Common Voltage Protection
-
Open Thermocouple Detection
-
Built-in Dual Watchdog
Specifications
CPU Module
|
Watchdog Timer
|
Module, Communication (Programmable)
|
Isolation
|
Intra-module Isolation
|
3000 VDC
|
EMS Protection
|
EFT (IEC 61000-4-4)
|
±4 kV for Power Line
|
ESD (IEC 61000-4-2)
|
±4 kV Contact for Each Terminal
|
LED Indicators
|
Status
|
1 x Power and Communication
|
Analog Input
|
Channels
|
8 Differential
|
Type
|
Voltage
Current
Thermocouple
|
Sensor Type
|
Thermocouple: J, K, T, E, R, S, B, N, C, L, M, LDIN43710
|
Range
|
Voltage: ±15 mV, ±50 mV, ±100 mV, ±150 mV, ±500 mV, ±1 V, ±2.5 V, ±5 V, ±10 V
Current: ±20 mA, 0 ~ +20 mA, +4 ~ +20 mA (Jumper selectable)
|
Resolution
|
16-bit
|
Accuracy
|
±0.1% of FSR
|
Sampling Rate
|
8 Hz (Total)
|
Input Impedance
|
Voltage: 2 MΩ
Current: 125 Ω
Thermocouple: > 400 kΩ
|
Common Voltage Protection
|
±200 VDC
|
Overvoltage Protection
|
240 Vrms
|
Individual Channel Configuration
|
Yes
|
Open Wire Detection
|
For Thermocouple Only (Software Selectable, *Note1)
|
COM Ports
|
Ports
|
1 x RS-485
|
Baud Rate
|
1200 ~ 115200 bps
|
Data Format
|
(N, 8, 1), (N, 8, 2), (E, 8, 1), or (O, 8, 1)
|
Protocol
|
Modbus RTU, DCON
|
Power
|
Reverse Polarity Protection
|
Yes
|
Input Range
|
+10 ~ +30 VDC
|
Consumption
|
1.2 W
|