Description
The M-7022 is a 12-bit, 2-channel Analog Output module that is designed for both voltage and current output using the ModbusRTU protocol (DCON an option via software). The M-7022 features 3000 Vdc intra-module isolation, and the power source for the current output can be selected as either internal or external via a jumper. Options are also provided to allow power-on and safe values to be set.
Features
- 2-channel Analog Output
- Software Selectable Current or Voltage Output
- Power-on Value Setting
- Safe Value Setting
- Open Wire Detection for Current Output
- Readback Voltage or Current
- 2 kV Channel to Channel Isolation
- 3000 VDC Intra-module Isolation
- Programmable Output Slope
- Dual Watchdog
- Wide Operating Temperature Range: -25 to +75°C
Specifications
I/O Specifications
Models | I-7022 | M-7022 | M-7022A | |
Analog Output | ||||
Channels | 2 | |||
Range | Voltage | 0 ~ +5 V, 0 ~ +10 V, | 0 ~ +5 V, 0 ~ +10 V, ±5 V, ±10 V | |
Current | 0 ~ +20 mA, +4 ~ +20 mA | |||
Resolution | 12-bit | |||
Accuracy | 0.1% | |||
Readback Accuracy | ±0.5% of FSR | |||
DA Output Response Time | 10 ms | |||
Programmable Output Slope | Voltage | 0.0625 ~ 1024.0 V/Second | ||
Current | 0.125 ~ 2048 mA/Second | |||
Current Load Resistance | Internal Power: 500 Ω | |||
External Power: 1050 Ω | ||||
Open Wire Detection (for current only) | Yes | |||
Channel-to-Channel Isolation | Yes, 2 kV | |||
Short Circuit Protection | Yes | |||
Power-on Value | Yes | |||
Safe Value | Yes |
System Specifications
Models | I-7022 | M-7022 | M-7022A |
Communication | |||
Interface | RS-485 | ||
RS-485 Bias Resistor | No (Usually supplied by the RS-485 Master. Alternatively, add a tM-SG4 or SG-785.) | ||
Format | (N, 8, 1) (N, 8, 2) (E, 8, 1) (O, 8, 1) | ||
Baud Rate | 1200 to 115200 bps | ||
Protocol | DCON | Modbus RTU, DCON | |
Dual Watchdog | Yes, Module (1.6 Seconds), Communication (Programmable) | ||
LED Indicator/Display | |||
System LED Indicator | Yes, 1 as Power/Communication Indicator | ||
I/O LED Indicator | - | ||
7-Segment LED Display | - | ||
Isolation | |||
Intra-Module Isolation, Field-to-Logic | 3000 VDC | ||
EMS Protection | |||
ESD (IEC 61000-4-2) |