Description
The M-7000 series is a family of network data acquisition and control modules that support Modbus RTU and DCON protocols. With the Modbus RTU protocol, the modules can easily communicate with most popular SCADA/ HMI software packages and PLC's. It has the same form factor as the I-7000 series.
The M-7061 provides 12 power relay output channels. There are options for configuring power-on and safe values. 4 kV ESD protection and 3750 VDC intra-module isolation are also provided to enhance the noise protection capabilities in industrial environment. The “D” versions of the 7061 series provide 12 LED indicators that can be used to monitor the status of the relay output channels. The M-7061 series are the ideal solution for high power applications.
Features
-
I-7061(D) and M-7061(D)
- 12-channel Power Relay Output
- 4 kV EFT Protection
- 3 kV Surge Protection
- Configurable Power-on Value Settings
- Configurable Safe Value Settings
- Dual Watchdog
- Wide Operating Temperature Range: -25 ~ +75°C
Specifications
Models | M-7061 | |
M-7061D | ||
Relay Output | ||
Channels | 12 (Form A) | |
Relay Type | Power Relay | |
Form A Relay | Contact Rating |
5 A @ 250 VAC 5 A @ 30 VDC |
Min. Contact Load | 10 mA @ 5 V | |
Contact Material | Silver TinAlloy | |
Operate Time | 10 ms | |
Release Time | 5 ms | |
Mechanical Endurance | 2 × 107 ops. | |
Electrical Endurance | 105 ops. | |
Surge Strength | 3000 VDC | |
Power-on Value | Yes | |
Safe Value | Yes |
Models | M-7061 |
M-7061D | |
Communication | |
Interface | RS-485 |
Format | (N, 8, 1), (N, 8, 2), (E, 8, 1), (O, 8, 1) |
Baud Rate | 1200 ~ 115200 bps |
Protocol | Modbus RTU, DCON |
Dual Watchdog | Yes, Module (1.6 Seconds), Communication (Programmable) |
LED Indicator/Display | |
System LED Indicator | Yes, 1 LED as Power/Communication Indicator |
I/O LED Indicators | - |
Yes, 12 LEDs as Digital Input/Relay Output Indicators | |
7-Segment LED Display | - |
Isolation | |
Intra-Module Isolation, Field-to-Logic | 3750 VDC |
EMS Protection | |
ESD (IEC 61000-4-2) | ±4 kV Contact for each Terminal |
±8 kV Air for Random Point | |
EFT (IEC 61000-4-4) | ±4 kV for Power Line |
Surge (IEC 61000-4-5) | ±3 kV for Power Line |
Power | |
Reverse Polarity Protection | Yes |
Input Range | 10 ~ 30 VDC |
Consumption | 1.7 W |
2.3 W | |
Mechanical | |
Dimensions (W x L x H) |