Description
PIR series modules have the ability to detect infrared waves generated by the human body within a diameter of approximately 8 meters, with a coverage area of 360° for indoor motion detection.
The modules can be configured to automatically switch on a light if motion is detected.
The modules also contain a temperature and humidity sensor for measuring indoor temperature and humidity, or it can be configured to activate a fire alarm.
A wide range of interface connections can be selected to suit individual needs, including RS-485/Ethernet/Wi-Fi, providing support for the DCON and Modbus RTU/TCP protocols, which can be easily integrated into existing HMI/SCADA/central control systems.
A free Utility is also included that allows configuration information and data to be displayed in a powerful chart format that can be exported to Microsoft Excel.
The screw-free quick-connect connector and the DIP and rotary switches make the modules easy to install, repair, and maintain. The casing of each module is made from UL94-V2 rated fireproof material, and the white minimalist exterior design ensures that it is easy to match with interior decoration.
Features
- Adjustable Time-Delay / Lux / Sensitivity
- Internal Photosensor for Smart Switch Control
- LED Indicator for PIR/Temperature Sensor
- Temperature Sensor for Measuring Room Temperature
- Suitable as either Temperature or Fire Alarm
- Relay Output Can be Used to Control Light Via the PIR/Temperature Sensor
- Suitable for loads up to 1500 W (Incandescent) and 300 W (Fluorescent)
- Fluorescent (T8) Loading Capability
- Wide range of Communication Interfaces and Protocols
- Ceiling or Surface-Mount Design
- Power-over-Ethernet (PoE) capable
Specifications
Model | PIR-230-E | ||
Motion and Occupancy Sensor | |||
Delay Time |
Hardware: 8-step Switch-selectable (seconds): 6, 16, 33, 66, 131, 262, 524, 1049 Software: 16-step (seconds): 2, 4, 6, 8, 16, 33, 49, 66, 131, 262, 393, 524, 1049, 2097, 3146, 4194 |
||
Lux Control Level | Hardware: 2 mode (Dawn and dust) / Software: 5-step | ||
Detection Height | 4 m Max. | ||
Motion Detection Field of View | 360°; 8 m Diameter Max. | ||
Occupancy Detection Field of View | - | ||
PIR Response Time | 1 second | ||
Temperature Sensor | |||
Measurement Range | -40 to +120°C | ||
Fire Alarm | 65°C (Programmable) | ||
Resolution | 0.01°C | ||
Accuracy | ±0.5°C (at 0 to 60°C) | ||
Relative Humidity Measurement | |||
Range | 0 to 100% RH | ||
Resolution | 0.1% RH | ||
Accuracy | ±5% RH | ||
Digital Input | |||
Channels | 2 | ||
Type | Wet | ||
On Voltage Level | 70 to 220 VAC | ||
Off Voltage Level | 20 VAC Max. | ||
Input Impedance | 68 KΩ, 1 W | ||
Relay Output | |||
Channels | 1 | ||
Type | Power Relay, Form C | ||
Max. Load Current |
NO: 10 A @ 250 VAC NC: 6 A @ 250 VAC |
||
Load Wattage | Incandescent Bulb: 1500 W Max.; Fluorescent Lamp: 300 W Max. | ||
Communication | |||
Node Address | Hardware: 160 to 191 / Software: 1 to 255 | ||
Protocol | DCON, Modbus RTU, Modbus TCP | ||
Wire Interface | Yes, RS-485 X 1 and Ethernet/PoE X1 | ||
LED Indicators | |||
LED Indicators | Yes,1 as Power/Communication Indicator. 1 as Alarm Indicator. | ||
EMS Protection | |||
ESD (IEC 61000-4-2) | ±4 kV Contact for each Terminal, ±8 kV Air for Random Point | ||
EFT (IEC 61000-4-4) | ±4 kV for Power Line | ||
Power Requirements | |||
Power supply | 18 to 48 VDC, PoE | ||
Reverse Polarity Protection |