PM-3033-CPS 3-phase Compact Smart Energy Meter for 1A/5A sec. CT's, CANopen


Price:
Sale price£245.00

Description

The PM-3033 series is part of a range of Powerful, cost-effective & advanced Smart Power Meters,  that gives you access to real-time electric usage for three-phase power measurement. With its high accuracy (<0.5%, PF=1 ), the PM-3033 series can be applied to both low voltage primary side and/or medium/high voltage secondary side and enables the users to obtain reliable and accurate energy consumption readings from the monitored equipments in real time under operation.

Direct input from “secondary side 1A/5A” type CTs. Dedicated CTs are no longer needed, which lowers the cost of implementation. It operates over a wide input voltage range 10 ~ 500 VAC offering maximum compatibility. It also supports Modbus RTU, Modbus TCP or CANopen protocols for easy integration.
PM-3033 Application

Features

  • True RMS Power Measurements
  • Energy Analysis for 3P4W, 3P3W, 1P3W, 1P2W
  • Direct input of secondary side 1A/5A CT
  • Voltage Measurements Up to 500 V
  • W Accuracy Better than 0.5% (PF=1)
  • Supports RS-485, Ethernet (PoE) or CANopen Interface
  • Supports Modbus RTU, Modbus TCP or CANopen Protocol
  • Total Harmonic Distortion (THD)
  • IEC 61010-1 and EN 61010-1

Specifications

Model PM-3033 PM-3033-MTCP PM-3033-CPS
AC Power Measurement
Wiring 3P4W-3CT, 3P3W-2CT, 3P3W-3CT, 1P2W-1CT, 1P3W-2CT
Measurement Voltage 10 ~ 500 V
Measurement Current 1A or 5A
Measurement Frequency 50/60 Hz
W Accuracy Better than 0.5% (PF=1)
Power Parameter Measurement True RMS voltage (Vrms), True RMS current (Irms), Active Power (kW), Active Energy (kWh), Apparent Power (kVA), Apparent Energy (kVAh), Reactive Power (kVAR), Reactive Energy (kVARh), Power Factor (PF), Frequency
Data Update Rate 1 Second
Communication
RS-485 Protocol Modbus-RTU - -
Baud rate 9600,19200 (default), 38400, 115200;
DIP Switch Selectable
- -
Data format N,8,1 (default); N,8,2; E,8,1; E,8,2; O,8,1; O,8,2 - -
Isolation 3000 VDC - -
Ethernet (PoE) Protocol - Modbus TCP -
CANopen Protocol - - CANopen
Baud rate - - 125 k (default), 250 k, 500 k, 1 M;
DIP Switch Selectable
Isolation - - 3000 VDC
Power
Input Range +12 ~ 48 VDC +12 ~ 48 VDC or PoE +12 ~ 48 VDC
Power Consumption 2 W
Mechanical
Casing Plastic
Dimensions (W x L x H) 127 mm x 105 mm x 33 mm
Module Installation DIN-Rail Mounting
Environment
Operating Temperature -20 ~ +70 °C
Storage Temperature

Estimate shipping