Description
It's always difficult but crucial to figure out how much energy is being consumed. The PM-313x series is a powerful, cost-effective, advanced range of Compact Power Meters.
![]() |
With its high accuracy (0.5%, PF=1), the PM-313x series products can be applied both on low voltage primary side and/or medium/high voltage secondary side and enable the users to obtain in real time the reliable and accurate energy consumption readings from the monitored equipment. These compact sized and cost effective Power Meters are equipped with revolutionary wired clip-on CT (various types support input current up to 200A) and standard RS485 Modbus communication protocol for easy deployment. It works with input voltages ranging 10V ~ 500V, supporting a wide range of applications. |
The PM-313X family comes in a full range of Single-phase and Three-phase compact power meters for power monitoring. The products offer a rich feature set combined with easy-to-integrate communications. They can easily be combined with our Data Logging and Data Acquisition products for a complete solution, such as our Orchestrator SCADA software or the PMC/PMD Power Meter Concentrator Units.
The PM-313x series also come with 2 channels of relay outputs, which can be linked with sirens or lights for alarm indication. It supports Modbus RTU protocol (with Modbus TCP or CAN bus also available) for easy integration.
Features
- True RMS energy and power parameter measurements.
- Energy Analysis for 3P4W, 3P3W, 1P3W, 1P2W wiring.
- Easy wiring for on-line installation.
- Supports RS-485 communication (Modbus RTU protocol)
- Wh accuracy better than 0.5%(PF=1).
- With wired clip-on CT (various types support input current up to 200A).
- Voltage Measurements Up to 500 V
- Compact DIN-Rail Mounting Enclosure
-
Also available:
Ethernet Communications (ModbusTCP)
CAN Bus (CANopen) - Supports 2 Power Relay Output (Form A)
Specifications
Model | PM-3133 | PM-3133-MTCP |
PM-3133-CAN PM-3133-CPS |
|
AC Power Measurement | ||||
Wiring | 3P4W-3CT, 3P3W-2CT, 3P3W-3CT, 1P2W-1CT, 1P3W-2CT | |||
Input Voltage | 10 ~ 500 V | |||
Input Current | CTØ10 mm (60 A); CTØ16 mm (100 A); CTØ24 mm (200 A) | |||
Input Frequency | 50/60 Hz | |||
W Accuracy | Better than 0.5% (PF=1) | |||
Power Parameter Measurement | True RMS voltage (Vrms), True RMS current (Irms), Active Power (kW), Active Energy (kWh), Apparent Power (kVA), Apparent Energy (kVAh), Reactive Power (kVAR), Reactive Energy (kVARh), Power Factor (PF) | |||
Data Update Rate | 1 Second | |||
Communication | ||||
RS-485 | Protocol | Modbus-RTU | - | - |
Baud rate |
9600,19200 (default), 38400, 115200; DIP Switch Selectable |
- | - | |
Data format | N,8,1 | - | - | |
Isolation | 2500 VDC | - | - | |
Ethernet | Protocol | - | Modbus TCP | - |
CAN Bus | Protocol | - | - | CAN and CANopen |
Baud rate | - | - |
125 k (default), 250 k, 500 k, 1 M; DIP Switch Selectable |
|
Isolation | - | - | 2500 VDC | |
Alarm Output | ||||
Power Relay | Form A (Normal Open) x 2; Relay Contact Voltage Range: 5 A @ 250 VAC (47 ~ 63Hz), 5 A @ 30 VDC | |||
Power | ||||
Input Range | +12 ~ 48 VDC | |||
Power Consumption | 4 W | |||
Mechanical | ||||
Casing | Plastic | |||
Dimensions (W x L x H) | 127 mm x 105 mm x 33 mm | |||