Description
The Electronic Switch Pulse Input Adapter connects sensors with pulse outputs to loggers with smart-sensor inputs. This Smart Sensor is compatible with electronic switch closures such as FET or open-collector outputs, or CMOS-level logic signals with a maximum input frequency of 120 Hz (120 pulses per second).
For Contact Closure type meters, please click here for the S-UCD-M006 .
Features
- Plug-n-play adapter for pulse output sensors
- Automatically recognized by HOBO Energy Logger
- 6m cable length (extension cables available)
Specifications
- Maximum Input Frequency: 120 Hz (120 pulses per second)
- Measurement Range: 0 – 65,533 pulses per logging interval
- Resolution: 1 pulse
- Lockout time: 45 µs ± 10%
- Recommended Input Type: Electronic solid state switch closure or CMOS-level digital output (example: FET, opto-FET or open collector)
- Preferred Switch State: Active low input Normally open
- Edge Detection: Falling edge, Schmitt Trigger buffer (logic levels: low ≤ 0.6 V, high ≥ 2.7 V)
- Minimum Pulse Width: 1 ms
- Input/Output Impedance: 100 KΩ
- Open Circuit Input Voltage: 3.3 V
- Maximum Input Voltage: 3.6 V
- User Connection: 24 AWG wires, 2 leads: white(+), black(-)
- Operating Temperature Range: -40° to 75°C (-40° to 167°F)
- Overall Cable Length: 6.5 m (21 ft.)
- Housing: Weatherproof PVC housing protects input adapter electronics
- Housing Dimensions: 14 x 0.95 cm (5.5 x 0.375 in.)
- Weight: 310 g (11 oz.)
- Bits per Sample 16
- Number of Data Channels: 1
- Measurement Averaging Option: No (reports the number of pulses over the logging interval)