Description
These Solid-State Current Transducers convert a primary AC circuit current to a proportional Analog signal (0-10Vdc), which allows the Current Usage to be monitored by a wide range of Data Loggers plus Data Acquisition, SCADA and BMS Systems. They are used to monitor the current for Electrical loads such as pumps, conveyors, machines or fans.
The SCG-651 series of current sensors require no external power, as they are totally powered by induction from the AC line being monitored. The sensors are typically used to monitor motor operation and can be used to determine motor failure, belt loss, machine feed rates or tool wear.
The SCG-651 series are Split-core to allow for easy retro-fitting and are available in 2 Range selectable version (R1 & R2) + a 200A version.
R1 version = 0-20A, 0-40A, 0-60A
R2 version = 0-50A, 0-100A, 0-150A
IMPORTANT: Please specify the range required in the comments section of your order.
Features
- Split-core for easy retrofit
- Compact Size
- Self Powered
- 0-10Vdc proportional Output
-
3 variants available:
R1 version = 0-20A, 0-40A, 0-60A
R2 version = 0-50A, 0-100A, 0-150A
200A - 20.3mm diameter conductor hole
Specifications
-
Measurement Range:
SC-651-R1: 0-20/40/60 Amps
SC-651-R2: 0-50/100/150 Amps
SC-651-200: 0-200 Amps -
Maximum Input Current:
SC-651-R1: 100 Amps Continuous
SC-651-R2: 150 Amps Continuous
SC-651-200: 225 Amps Continuous -
Accuracy:
SC-651-R1/R2: ± 2% FSO (5-100% of range)
SC-651-200: ± 1% FSO (5-100% of range) -
Signal Output: 0-10 Vdc
-
Sensor Power: Self-powered
-
Insulation Class: 600 Vac, insulated conductors
-
Frequency: 50/60 Hz
-
Response Time: 200 mS Typical, 0-90 %
-
Output Load:1 MΩ typical
-
Loading Error: add 0.5% error with 100KΩ
-
Operating Temperature: -15 to 60 °C (5 to 140 °F)
-
Operating Humidity: 5 to 90% RH non-condensing
-
Terminal Block:14 to 22 AWG
-
Dimensions:76 x 79 x 24.9 mm (3.0 x 3.1 x 0.98 in)
-
Sensor Aperture: 20.3 mm (0.8 in)
-
Enclosure Material: ABS/PC, UL94 V-0
-
Agency Approvals: cULus Listed
Technical
SCG-651 Current Transducer Datasheet
Applications
- Energy Usage
- Process monitoring
- Monitoring Motor/machine wear to schedule maintenance/improve reliability
For a complete solution, please talk to us about our Orchestrator SCADA Monitoring software and Data Acquisition products.