Description
The SG-3013 is a RTD input signal conditioning module to transform RTD input to voltage or current output. SG-3013 uses a microprocessor-based transducer, which integrating two high resolution ADCs and an MCU, to acquire the RTD signal. The supported RTD types are Pt100 , Pt1000 , Ni 120 ,Cu100 ,and Cu1000.
The SG-3013 supports 1000Vdc 3-way isolation. The power supply that drives the module's input and output circuitry is internally isolated, enabling SG-3013 to offer true channel - to - channel isolation.
It's easy to mount the SG-3013 on a standard DIN rail and it can operate in environments with wide temperature ranges.
Specifications
Analog Input
- Input Channels: 1
- Input Type: Pt100 α=0.00385 / Pt100 α=0.003916 / Ni 120 / Pt1000 α=0.00385
- Input Connections: 2/3/4 Wires
- Accuracy: ±0.1% of full range
- Three-way isolation: 1000Vdc
Analog Output
- Channels: 1
- Voltage Output (Unipolar): 0~5V,0~10V (Output impedance : <50Ω)
- Current Output: 0 ~ 20mA, 4 ~ 20mA
- Current load resistor: 0~500Ω(Source)
Other Specifications
- Weight: 94 gram
- LED Display: 1 LED as Power/ Communication indicator
- Power Input: +10 to +30 Vdc
- Power Consumption: 1.2W
Environment
- Operating temperature: -25°C to 75°C
- Storage temperature: -30°C to 75°C
- Humidity: 5 to 95%, non-condensing
Switch |
Temperature Range (°C) |
||
RTD Type Platinum 100,α= 0.00385 | |||
1 |
0x00 |
00000 |
-200~200 |
2 |
0x01 |
10000 |
-200~600 |
3 |
0x02 |
01000 |
-100~100 |
4 |
0x03 |
11000 |
-100~0 |
5 |
0x04 |
00100 |
-100~200 |
6 |
0x05 |
10100 |
-50~50 |
7 |
0x06 |
01100 |
-50~150 |
8 |
0x07 |
11100 |
0~100 |
9 |
0x08 |
00010 |
0~200 |
10 |
0x09 |
10010 |
0~600 |
RTD Type Platinum 100,α= 0.003916 | |||
11 |
0X0A |
01010 |
-200~200 |
12 |
0X0B |
11010 |
-200~600 |
13 |
0X0C |
00110 |
-100~100 |
14 |
0X0D |
10110 |
-100~0 |
15 |
0X0E |
01110 |
-100~200 |
16 |
0X0F |
11110 |
-50~50 |
17 |
0x10 |
00001 |
-50~150 |
18 |
0x11 |
10001 |
0~100 |
19 |
0x12 |
01001 |
0~200 |
20 |
0x13 |
11001 |
0~600 |
RTD Type Platinum 1000,α= 0.00385 | |||
21 |
0x14 |
00101 |
-200 ~ 600 |
RTD Type Nickel 120 |
|||
22 |
0x15 |
10101 |
-80 ~ 100 |
23 |
0x16 |
01101 |
0 ~ 100 |
24 |
0x17 |
11101 |
0~300 |
25 |
0x18 |
00011 |
-80~300 |
RTD Type Cu 100 at 0°C,α= 0.00421 |
|||
26 |
0x19 |
10011 |
-20 ~ 150 |
RTD Type Cu 100 at 25°C,α= 0.00427 |
|||
27 |
0x1A |
01011 |
0 ~ 200 |
RTD Type Cu 1000 at 0°C,α= 0.00421 |
|||
28 |
0X1B |
11011 |
-20 ~ 150 |