XV308 Analog input (8AI) +Digital I/O (8DIO) Daughter Board


Price:
Sale price£128.00

Description

The XV308 provides 8 channels for analog input and 8 channels for universal digital input/output. Analog Input channels are Single-ended type and provide a programmable input range (±1 V, ±2.5 V, ±5 V, ±10 V, ±20 mA, 0 ~ 20 mA, 4 ~ 20 mA). Each Analog Input channels also provides a high overvoltage protection of 120 VDC. Universal digital input/output can be selected via wire connections. Digital input channels are sourcetype and can be used as 32-bit counters. Digital output channels are sink-type with short circuit protection and options for configuring power-on digital output values.

 

For WISE-5231 Controller/Logger, PMC-5231 Power Meter Concentrator & VPD Series HMI Displays 

Features

  • 8-channel Analog Input
  • 8-channel Universal Digital Input/Output
  • Digital Input Channels can be used as 32-bit Counters
  • Configurable Power-on Value Settings
  • Open Wire Detection for 4 ~ 20 mA
  • Individual Channel Configuration
  • 120 VDC Overvoltage Protection for Analog Input
  • 60 VDC Overvoltage Protection for Digital Input
  • Overload Protection for Digital Output
  • Short-circuit Protection for Digital Output

Specifications

I/O Specifications

Analog Input
Channels 8
Type ±1 V, ±2.5 V, ±5 V, ±10 V, ±20 mA, 0 ~ 20 mA, 4 ~ 20 mA (Jumper Selectable)
Resolution 16-bit
Sampling Rate Normal Mode 10 Hz
Fast Mode 200 Hz
Accuracy Normal Mode ±0.1 %
Fast Mode ±0.5 %
Input Impedance 20 MΩ
Overvoltage Protection 120 VDC
Universal Digital Input/Output
Channels Digital Input and Digital Output=8 (By Wire Connection)
Digital Input Wet Contact On Voltage Level +1 VDC Max.
Off Voltage Level +4 ~ 30 VDC
Dry Contact On Voltage Level Close to GND
Off Voltage Level Open
Counters Max. Count 32-bit (0~4,294,967,285)
Max. Input Frequency 50 Hz
Min. Pulse Width 10 ms
Overvoltage Protection 60 VDC
Digital Output Output Type Sink
Max. Load Current 700 mA
Load Voltage 3.5 ~ 50 VDC
Overvoltage Protection 60 VDC
Overload Protection Yes
Short Circuit Protection Yes
Power-on Value Yes, Programmable

System Specifications

Communication
Interface RS-232/TTL
Format N, 8, 1
Baud Rate 115200 bps
Protocol Modbus/RTU
Isolation
Intra-module Isolation, Field-to-Logic 2000

Estimate shipping

You may also like