XV310 Analog (4AI/4AO) +Digital I/O (4DI/4DO) Daughter Board


Price:
Sale price£153.00

Description

The XV310 is a multifunction expansion board that includes 4 analog input channels, 2 analog output channels, 4 digital input channels and 4 digital output channels.

It provides a programmable input range on all analog input channels (+/-1 V, +/-2.5 V, +/-5 V, +/-10 V, +/-20 mA, 0 ~ 20 mA or 4 ~ 20 mA), analog output channels are 12- bit at +/-5 V, +/-10 V, 0 ~ 20 mA or 4 ~ 20 mA. Each analog input channel can be configured for an individual range and provides a high overvoltage protection of 120 VDC. Voltage and current inputs/outputs are jumper selectable.



For WISE-5231 Controller/Logger, PMC-5231 Power Meter Concentrator & VPD Series HMI Displays 

Features

  • Multifunction (4 AI, 2 AO, 4 DI, 4 DO)
  • Individual Channel Configuration
  • Jumper Selectable Voltage or Current Input/Output
  • Open Wire Detection for Current Output
  • Configurable Power-on Value Settings
  • Digital Input Channels can be used as 32-bit Counters
  • 120 VDC Overvoltage Protection for Analog Input
  • 60 VDC Overvoltage Protection for Digital Input
  • Overload Protection for Digital Output
  • Short-circuit Protection for Digital Output

Specifications

I/O Specifications

Analog Input
Channels 4
Type ±1 V, ±2.5 V, ±5 V, ±10 V, ±20 mA, 0 ~ 20 mA, 4 ~ 20 mA (Jumper Selectable)
Resolution 16-bit
Sampling Rate Normal Mode 10 Hz
Fast Mode 200 Hz
Accuracy Normal Mode ±0.1 %
Fast Mode ±0.5 %
Overvoltage Protection 120 VDC
Analog Output
Channels 2
Type 0 V ~ +5 V, ±5 V, 0 V ~ +10 V, ±10 V, 0 mA ~ +20 mA, +4 mA ~ +20 mA (Jumper Selectable)
Resolution 12-bit
Accuracy ±0.1 %
Voltage Ouput Capability 10 V @ 20 mA
Current Load Resistance 500 Ω
Digital Input
Channels 4
Type Dry Contact Source
Wet Contact -
On Voltage Level Dry Contact Close to GND
Wet Contact -
Off Voltage Level Dry Contact Open
Wet Contact -
Input Impedance -
Counters Max. Count 32-bit (0~4,294,967,285)
Max. Input Frequency 50 Hz
Min. Pulse Width 10 ms
Overvoltage Protection 60 VDC
Digital Output
Channels 4
Type Source
Max. Load Current 650 mA/channel
Load Voltage +10 to +40 VDC
Overvoltage Protection 47 VDC
Overload Protection

Estimate shipping